How to Rescan Plc and New BootProject? |RescanPlcNewBootProject|Beckhoff|TwinCAT2 PLC download and update
1 Delete Boot Project
Go online with current PLC project and delete current Boot Project.
2 “Clean all”
Select function “Clean all” at PLC project.
Confirm 1. Message box with “Ja”
Confirm 2. Message box with “Nein”
This will delete the Var config created by last scanning in System Manager
3 “Rebuild all”
Select function “Rebuild all” at PLC project.
Warning 1990: no ‘VAR_CONFIG’ for ‘xxx’ appears for all variables with
var config, ignore this.
4 Scan PLC Project and restart
Scan / Rescan PLC Project in Systemmanager
Check PLC Settings
Generate mappings, Check configuration, Activate configuration and Restart
System in Run Mode
Following Error Message will appear. Click on “OK” Button.
5 “Rebuild all” again
Warning 1990: no ‘VAR_CONFIG’ for ‘xxx’ disappears for all variables
with var config.
6 Create Boot Project
Go online. Click on “Yes” button at following Message box.
Start PLC by F5 Button.
Save and create Boot Project.